ANALISA SISTEM PROTEKSI UNTUK KORDINASI RELAY ARUS LEBIH PADA GARDU INDUK KOTA DILI,TIMOR LESTE DENGAN MENGGUNAKAN SOFTWARE ETAP POWER STATION

Cabral, Deciderio Ernie de Jesus (2018) ANALISA SISTEM PROTEKSI UNTUK KORDINASI RELAY ARUS LEBIH PADA GARDU INDUK KOTA DILI,TIMOR LESTE DENGAN MENGGUNAKAN SOFTWARE ETAP POWER STATION. Skripsi thesis, Institut Teknologi Nasional Malang.

[img] Text
BAB I.pdf
Restricted to Registered users only
Available under License Creative Commons Attribution Non-commercial Share Alike.

Download (182kB) | Request a copy
[img] Text
BAB II.pdf
Restricted to Registered users only
Available under License Creative Commons Attribution Non-commercial Share Alike.

Download (563kB) | Request a copy
[img] Text
BAB V.pdf
Restricted to Registered users only
Available under License Creative Commons Attribution Non-commercial Share Alike.

Download (101kB) | Request a copy

Abstract

ANALISA SISTEM PROTEKSI UNTUK KORDINASI RELAY ARUS LEBIH PADA GARDU INDUK KOTA DILI,TIMOR LESTE DENGAN MENGGUNAKAN SOFTWARE ETAP POWER STATION Deciderio Ernie de Jesus Cabral Teguh Herbasuki Taufik Hidayat Dedycabral23@gmail.com ABSTRAK Sistem proteksi sangat penting untuk mengamankan peralatan listrik pada G.I kota Dili. Oleh sebab itu sistem tenaga listrik di G.I kota Dili haruslah terkordiasi dengan aman. Gangguan yang biasanya terjadi antara lain gangguan sismetris dan asimetris yang tidak dapat di hindarkan pada sistem distribusi eksternal. Rele yang digunakan adalah OCR sebagai proteksi pada feeder. Pada feeder 1 dan 3 sisi 20 kV mengalami kegagalan memutus saat gangguan terjadi. Untuk meningkatkan keandalan proteksi di G.I kota Dili, yaitu dengan mensetting ulang relenya. Kemudian dirubah sesuai perhitugan OCR pada sisi 20 kV, sesudah di setting OCR 2 pada feeder 1 dengan waktu 2,1 detik dan arus sekundernya 0.43 ampere, untuk OCR 8 pada feeder 3 dengan waktu 1.6 detik dan arus sekunder 0.5 ampere. Agar semakin cepat memotong arus gangguan dan tidak merusak perelatan listrik lainya. Kata kunci --Over Current Relay, Feeder, Arus Gangguan. ANALYSIS OF THE PROTECTION SYSTEM FOR THE COORDINATION OF THE OVERCURRENT RELAYS OF THE MAIN SUBSTATION OF DILI CITY, TIMOR LESTE USING THE SOFTWARE ETAP POWER STATION Deciderio Ernie de Jesus Cabral Teguh Herbasuki Taufik Hidayat Dedycabral23@gmail.com ABSTRACT Protection system is very important to secure electrical equipment in Substation Dili city. Therefore the power system in Substation Dili city must be safely cordoned. Disturbances that usually occur, among others, asymmetrical and asymmetrical sismetris can not be avoided on the external distribution system. The relay used is OCR as a protection on the feeder. On feeder 1 and 3 side 20 kV failure to break when the disturbance occurs. To improve the reliability of protection in G.I Dili city, namely by setting up the relay. Then changed according to OCR calculation on 20 kV side, after setting feeder 1 with 2.1 seconds and secondary current 0.43 ampere, for feeder 3 with time of 1.6 seconds and secondary current of 0.5 ampere. In order to more quickly cut the flow of interference and not damage other electrical events. Keywords--Over Current Relay, Feeder,short circuit.

Item Type: Thesis (Skripsi)
Uncontrolled Keywords: Over Current Relay, Feeder, Arus Gangguan.
Subjects: Engineering > Electrical Engineering
Divisions: Fakultas Teknologi Industri > Teknik Elektro S1 > Teknik Elektro S1(Skripsi)
Depositing User: Ms Nunuk Yuli
Date Deposited: 16 Jan 2019 04:13
Last Modified: 06 Mar 2019 02:06
URI: http://eprints.itn.ac.id/id/eprint/206