ANALISA PREDIKSI INDEKS KEANDALAN MENGGUNAKAN METODE RELIABILITY INDEX ASSESSMENT (RIA) PADA JARINGAN DISTRIBUSI 20 kV KOTA DILI TIMOR -LESTE

Ximenes, Arlindo (2017) ANALISA PREDIKSI INDEKS KEANDALAN MENGGUNAKAN METODE RELIABILITY INDEX ASSESSMENT (RIA) PADA JARINGAN DISTRIBUSI 20 kV KOTA DILI TIMOR -LESTE. Skripsi thesis, Institut Teknologi Nasional Malang.

[img] Text
File Lengkap Skripsi PDF.pdf
Restricted to Registered users only
Available under License Creative Commons Attribution Non-commercial Share Alike.

Download (3MB) | Request a copy

Abstract

ANALISA PREDIKSI INDEKS KEANDALAN MENGGUNAKAN METODE RELIABILITY INDEX ASSESSMENT(RIA) PADA JARINGAN DISTRIBUSI 20 kV KOTA DILI TIMOR-LESTE Arlindo Ximenes (13.12.004) Desen Pembimbing : Dr. Irrine Budi S, ST, MT . 1 ) , Ir Eko Nurcahayo,MT. 2) Jurusan Teknik Elektro S-1 ,Institut Teknologi Nasional Malang aximenes482@gmail.com Abstrak Sering dengan kebutuhan Energi Listrik yang meningkat di Kota Dili, sistem distribusi diharuskan memiliki keandalan terhadap penyalur listrik ke konsumen, terutama pada kontiniutas pelayan daya . Pada tugas akhir ini analisa prediksi indeks keandalan kota Dili dengan metode Reliability Index Assesstement (RIA) , yaitu metode yang memperhatikan laju kegagalan untuk medapatkan indeks keandalan sistem tenaga listrik, sehingga hasil akhir dari metode ini lebih mendekati hasil sebenarnya di lapangan. Setelah keandalan kondisi Normal konfigurasi PT .PLN Kota Dili serta implementasi Automatic Circuit Recloser (ACR) untuk meninkatkan keandalan sistem Distribusi Kota Dili. Dengan menggunakan Metode (RIA) pada sistem distribusi Kota Dili maka akan didapatkan nilai indeks keandalan .Dapat dilihat pada saat kondisi normal konfigurasi PLN niali SAIFI sebesar 3.21 (Kali/Tahun) dan SAIDI sebesar 21 (Jam/Tahun) sedankan setelah menggunakan metode RIA didapatkan SAIFI sebesar 3.6377 (Kali/Tahun) dan SAIDI sebesar 25.2441 Jam/Tahun, jika dilihat telah dilakukan terlihat ada perbedaan yang cukup siknifikan, disebabkan karena pada metode RIA mendata kegagalan yang terjadi pada peralatan secara konprehensif. Untuk meningkatkan keandalan dilakukan implementasi ACR pada penyulang dan didapat indeks keandalan palin optimal yaitu SAIFI 2.3970 (Kali/Tahun), SAIDI 20.0051 (Jam/Tahun). Kata Kunci : Keandalan , Reliability Index Assessment (RIA) , ETAP Power Station Sistem Distribusi 20 kv PT. PLN Kota Dili, Automatic Circuit Recloser (ACR) iii PREDICTION ANALYSIS OF RELIABILITY INDEX USING RELIABILITY INDEX ASSESSMENT (RIA) METHOD ON DISTRIBUTION NETWORK 20 kV DILI TIMOR-LESTE CITY Arlindo Ximenes (13.12.004) Desen Pembimbing : Dr. Irrine Budi S, ST, MT . 1 ) , Ir Eko Nurcahayo,MT. 2) Jurusan Teknik Elektro S-1 ,Institut Teknologi Nasional Malang aximenes482@gmail.com Abstrak Frequently with the need for increased Electrical Energy in Dili City, distribution systems are required to have reliability against the power supply to the consumer, especially in the power supply contini- tion. In this final project, Dili reliability index prediction analysis using Reliability Index Assessment (RIA) method is a method that takes into account the failure rate to obtain the reliability index of power system, so the final result of this method is closer to the actual result in the field. After reliability of Normal condition of PT .PLN Dili and implementation of Automatic Circuit Recloser (ACR) to improve reliability of Dili Distribution System. By using Method (RIA) at distribution system of Dili City hence will get value of index of reliability. Can be seen at normal condition of configuration of PLN niali SAIFI equal to 3.21 (Times / Year) and SAIDI equal to 21 (Hour / Year) after using RIA method got SAIFI of 3.6377 (Kali / Year) and SAIDI of 25.2441 Hour / Year, if seen has been done visible there is a significant difference, because the RIA method to record the failure of the equipment in a comprehensive manner. To improve the reliability of ACR implementation on the repeater and obtained index of optimal palm reliability is SAIFI 2.3970 (Kali Year), SAIDI 20.0051 (Hours/ Year). Key words: Reliability, Reliability Index Assessment (RIA), ETAP Power Station Distribution System 20 kv PT. PLN Dili City, Automatic Circuit Recloser (ACR).

Item Type: Thesis (Skripsi)
Uncontrolled Keywords: Keandalan , Reliability Index Assessment (RIA) , ETAP Power Station Sistem Distribusi 20 kv PT. PLN Kota Dili, Automatic Circuit Recloser (ACR)
Subjects: Engineering > Electrical Engineering
Divisions: Fakultas Teknologi Industri > Teknik Elektro S1 > Teknik Elektro S1(Skripsi)
Depositing User: Ms Nunuk Yuli
Date Deposited: 31 Jul 2019 02:03
Last Modified: 31 Jul 2019 02:03
URI: http://eprints.itn.ac.id/id/eprint/3692