Sulistiawati, Irrine Budi and Rosidin, Khaikal Mudatsir and Lomi, Abraham (2017) Dynamic Stability Modified IEEE 3 Generator 9 Bus With 50 MW Power Injection of Generator XY. In: International Seminar on Intellligent Technology and its Applications, 28-29 Agustus 2017, ITS Surabaya.
Text
10. isitia khaikal.pdf Download (1MB) |
|
Text (Ujiplagiasi)
10. isitia khaikal.pdf.pdf Download (2MB) |
|
Text
Peer review Paper 8.pdf Download (1MB) |
|
Text
C.2.a.2-13_artikel_LOMI.pdf Download (1MB) |
|
Text
prosiding_artikel-13_C.2.a.2-13_cek plagiasi.pdf Download (1MB) |
Abstract
The existence of new power injection at a system will effect system stability that existed before, so stability analyze was needed to know the system conditioning before and after power injection, and performance system after disturbance, by observe rotor angle, frequency, and voltage. The result of dynamic system show that power injection of Gen XY can supply 0,021 pu at bus 1, 0,001 at bus 2, 0,001 at bus 3, 0,0261 pu at bus 4, 0,0366 pu at bus 5, 0,0186 pu at bus 6, 0,0101 pu at bus 7, 0,0083 pu at bus 8, 0,0061 pu at bus 9. When 3 phase fault during 1-2 second happened, the frequency and rotor angle increasing. When generator XY inject system with 50 MW, the modified IEEE 3 Generator 9 Bus become increase with frequency 60.27 Hz, voltage profile increasing, rotor angle decreased close to normal conditions.
Item Type: | Conference or Workshop Item (Paper) |
---|---|
Uncontrolled Keywords: | Dynamic system stability; power injection; frequency stability; voltage stability; rotor angle stability |
Subjects: | Engineering > Electrical Engineering |
Divisions: | Fakultas Teknologi Industri > Teknik Elektro S1 |
Depositing User: | Mr Sayekti Aditya Endra |
Date Deposited: | 05 Nov 2019 02:51 |
Last Modified: | 25 Apr 2023 13:26 |
URI: | http://eprints.itn.ac.id/id/eprint/4426 |
Actions (login required)
View Item |