SISTEM KOORDINASI OVER CURRENT RELAY (OCR) UNTUK MENGATASI HUBUNG SINGKAT PADA PEMBANGKIT LISTRIK TENAGA DIESEL DI PT. PLN (PERSERO) SEKTOR LOMBOK

Ambara, Akhmad (2018) SISTEM KOORDINASI OVER CURRENT RELAY (OCR) UNTUK MENGATASI HUBUNG SINGKAT PADA PEMBANGKIT LISTRIK TENAGA DIESEL DI PT. PLN (PERSERO) SEKTOR LOMBOK. Skripsi thesis, Institut Teknologi Nasional Malang.

[img] Text
19. FILE LENGKAP SKRIPSI..pdf
Restricted to Registered users only
Available under License Creative Commons Attribution Non-commercial Share Alike.

Download (4MB) | Request a copy

Abstract

Sistem Koordinasi Over Current Relay (OCR) Dan GFR Untuk Mengatasi Hubung Singkat Pada Pembangkit Listrik Tenaga Diesel Di PT. PLN (Persero) Sektor Lombok Akhmad Ambara Teguh Herbasuki Taufik Hidayat ambara_ahmad@yahoo.com ABSTRAK System proteksi yang beroperasi secara kontinyu sangat dibutuhkan untuk melindungi sistem pada generator dari gangguan, baik itu gangguan internal maupun gangguan eksternal. Untuk menghindari hubung singkat di PLTD Ampenan Sektor Lombok, dengan salah satu cara yaitu mensetting ulang relay khususnya pada perangkat pembangkit yang di pasang pada terminal Generator . Relay OCR pada generator 3 Unit, sebelumnya disetting dengan waktu 5 detik dan arus 3,93 A dirubah menjadi 3,27 detik dan arus 2,93 A, pada generator Unit 4 sebelumnya disetting dengan waktu 0,05 detik dan arus 0,493 A dirubah menjadi 0,4 detik dan arus 0,451 A, sedangkan pada Generator 4 Unit setting awal waktu 5 detik dan arus 3,93 A dirubah menjadi 4,4 detik dan arus 3,62 A agar semakin cepat untuk memotong arus gangguan dan tidak sampai merusak generator. Untuk settingan relay GFR dengan waktu diperpanjang dari 0,2 detik menjadi 0,4 detik dan settingan sensitifitas relay GFR diperbesar dari 0% menjadi 15% sehingga relay GFR menjadi baik dalam beroperasi. Kata Kunci : Generator, Proteksi, Hubung Singkat, OCR, GFR iii Coordination System Over Current Relay (OCR) And The GFR To Overcome A Short Circuit On A Diesel Power Plant In PT. PLN (Persero) Lombok's Sector Akhmad Ambara Teguh Herbasuki Taufik Hidayat ambara_ahmad@yahoo.com ABSTRACT Protection system that operates continuously is urgently needed to protect the generator from interference, be it internal or external disturbance disorders. To avoid a short circuit in DIESEL POWER Sector Ampenan Lombok, with one way i.e. setting up reset relay device, especially at a plant in pairs on a Generator terminal. OCR on generator relay 3 units, previously gives a chance to the time of 5 seconds and A 3.93 flow changed to 3.27 seconds and current 2.93 A, on a previous Unit 4 generator gives a chance to the time of 0.05 seconds and current 0.493 A changed to 0.4 seconds and current 0.451 à While on the initial setting Unit 4 Generator time of 5 seconds and A 3.93 flow changed to 4.4 seconds and the current 3.62 A so the sooner to cut the current disorder and not to damage the generator. For setting the relay with a time of GFR is extended from 0.2 seconds to 0.4 seconds and setting sensitivity relay GFR enlarged from 0% to 15% so be good in GFR relay operates. Keywords: Generator, Protection, Short Circuit, OCR, GFR

Item Type: Thesis (Skripsi)
Uncontrolled Keywords: Generator, Protection, Short Circuit, OCR, GFR
Subjects: Engineering > Electrical Engineering
Divisions: Fakultas Teknologi Industri > Teknik Elektro S1 > Teknik Elektro S1(Skripsi)
Depositing User: Ms Nunuk Yuli
Date Deposited: 21 Feb 2019 03:47
Last Modified: 06 Mar 2019 01:50