Influence of Adding BESS as Ancillary Controller of Wind Power Plant on Low Frequency Oscillation

Setiadi, Herlambang and Asfani, Dimas Anton and Nasution, Tigor Hamonangan and Suyono, Hadi and Putranto, Lesnanto Multa and Krismanto, Awan Uji and Abdillah, Muhammad (2021) Influence of Adding BESS as Ancillary Controller of Wind Power Plant on Low Frequency Oscillation. Influence of Adding BESS as Ancillary Controller of Wind Power Plant on Low Frequency Oscillation. pp. 1-11.

[img] Text
Influence of Adding BESS as Ancillary Controller of Wind Power Plant on Low.pdf
Available under License Creative Commons Attribution Non-commercial Share Alike.

Download (1MB)
[img] Text
Influence_of_adding_BESS_as_Ancillary_Controller_of_Wind_Power_Plant_on_Low.pdf
Available under License Creative Commons Attribution Non-commercial Share Alike.

Download (1MB)
[img] Text
Peer review Jurnal Ilmiah Influence of Adding 057.pdf
Available under License Creative Commons Attribution Non-commercial Share Alike.

Download (438kB)

Abstract

Abstract: This paper introduces the influence on integrating battery energy storage system (BESS) as ancillary controller of wind power plant in small signal stability. Modified two area power system is used as the test system. The modification has been made by replacing one synchronous generator with wind and PV generation. Modal analysis and phase portrait analysis are used to investigate the influence of adding BESS on wind power plant. From the simulation results it is found that the small signal stability performance can be enhance by adding BESS as ancillary controller of wind power plant. This result indicated by increasing damping performance on the critical mode. Furthermore, the oscillatory condition is more damped compared to the base case scenarios. These results indicated by the smallest circular on the phase portrait analysis. Moreover, by adding BESS as ancillary controller the structured singular value (SSV) of the investigated system is 0.8321. It can be stated that the proposed method is robust against uncertainty (SSV must below 1). Keywords: BESS, Clean energy technology, Oscillatory stability.

Item Type: Article
Uncontrolled Keywords: Keywords: BESS, Clean energy technology, Oscillatory stability
Subjects: Engineering > Electrical Engineering
Divisions: Fakultas Teknologi Industri > Teknik Elektro S1
Depositing User: Ms Nunuk Yuli
Date Deposited: 17 Jan 2022 06:27
Last Modified: 20 Jan 2022 03:14
URI: http://eprints.itn.ac.id/id/eprint/6478